Hi,Furnace: Bryant upflow model 383k
I have a problem with my furnace blower continuing to blow.. it doesn't stop even after turning on and off the main switch.... i believe as a result the heater never starts....
the circuit board on this furnace comes with a led which explains the problem... "limit or flame rollout swithc is open- defective limit swithc or connections, open flame rollout switch-manual reset"
please advise i don't see a limit switch that i can toggle.
-- James (budsworld@hotmail.com), January 26, 2004
James! Just a guess---is the furnace sooted up--does the flame come out around the burners into the room? Insufficient combustion air will make the furnace burn "sooty" [too rich] and soot will clog the flues in the heat exchanger.If tha'ts all ok the you might check the flame rollout switch which should be located just above the burners on a shield. Try jumpin it ans see if it works. If so--get another switch. If not--call a repairman. Problems will probably be in the circuit board. Please let us know what you find out. old hoot. Matt. 24:44
-- oldhootgibson (oldhoot@shawneelink.net), January 29, 2004.
The flame rollout switch blowing, is a result of the blockage of the vent flu, causing the pressure to force flames from under the heat exchanger. The flame rollout switch is a manual fuse that is good only once, my suggestion is to call bryant and get the part number for a new switch. It must be manually replaced